Page 26 - Fireless
P. 26
ELESS PRODUCT GUIDE

14.0 Appendix

Appendix A – Channel Frequency Table

Channel MHz Channel MHz
1 868,050 7 868,775
2 868,150 8 868,875
3 868,250 9 868,975
4 868,350 10 869,075
5 868,450 11 869,175
6 868,550 12 869,475

Appendix B – Analogue Value Definitions

Displayed Value
1 Communications Lost
2 Battery Fault - Low (30 days)
3 Battery Fault - Removed/Failed (7 Days)
4 Removed/Tampered
5 General Fault
16 Normal Condition
25 Detector Normal
32 I/O Relay(s) or Sounder is Active/ON.
64 I/O Input High or Manual Call Point Alarm/Operated
80 Detector Alarm

Appendix C – Event log definitions

In normal use the WTR will store important operational information in its historic event log, which is
accessible from the user or engineers menu. The following codes and their definitions apply:

Event Event Event Description
Code Abbreviation
No event
0 000 Cold start
1 ON BrownOut Detection reset
2 BOD WatchDog reset
3 WDR User reset
4 FRS Battery replaced
5 005 Loop isolator activated
6 ISO Sounder loop activated
7 SAC Sounder activated
8 SLA EEPROM read-write error
9 009 Sounder loop deactivated
10 SLD Automatic alarm
15 ALM Manual alarm
16 ALM Tamper event
17 TAM Fault
18 FLT Primary battery voltage is low
19 PLO Secondary battery voltage is low
20 SLO Primary battery discharged
21 POF Secondary battery discharged
22 SOF Battery: 30 days left
23 30D Battery: 7 days left
24 7D Power supply fault
25 PSF Communication fault - device lost
32 C2F Communication error - status message didn't received
33 C1F Status message received from unassigned device
34 UNS Lost device recovered
35 COK Transponder time and date set
64 STT

Document No.: PEN-FL2-2 Date: 29/06/2016 Page 26 / 30